Container DataCenter Configuration
SIZE CDC | Container 6x3x3m E30/60 steel structure, Door100x200, RC3, Roxtec, Stairs | Container 6x3x3m E30/60 steel structure, Door100x200, RC3, Roxtec, Stairs | Container 6x3x3m E30/60 steel structure, Door100x200, RC3, Roxtec, Stairs | Container 6x3x3m E30/60 steel structure, Door100x200, RC3, Roxtec, Stairs |
Moc IT | 10kW | 15kW | 20kW | 30-40kW |
Power Supply / UPS | RGCDC Cab 250A, Backup PS-ATS, 2xEPO, Generator BPS2000, | RGCDC Cab 250A, Backup PS-ATS, 2xEPO, Generator BPS2000, | RGCDC Cab 250A, Backup PS-ATS, 2xEPO, Generator BPS2000, | RGCDC Cab 250A, Backup PS-ATS, 2xEPO, Generator BPS2000, |
Cooling | 12kW, iROW N+1, wall-mounted condensers | 17kW, iROW N+1, roof condensers | 21kW, iROW N+1, roof condensers | 40kW, iROW N+1, roof condensers |
Fire protection | Inergen/Novec/FM200 | Inergen/Novec/FM200 | Inergen/Novec/FM200 | Inergen/Novec/FM200 |
IT-RACK-st | 4CUBEDC 4x4DC42U600(3kW) + 1xRACK-UPS | 4CUBEDC 4x4DC42U600(3,5kW) + 1xRACK-UPS | 4CUBEDC 4x4DC42U600(5kW) + 1xRACK-UPS | 4CUBEDC 4x4DC42U600(7,5kW) + 1xRACK-UPS |
Security | CCTV, SKD, SSWIN, EMS, SM4DC | CCTV, SKD, SSWIN, EMS, SM4DC | CCTV, SKD, SSWIN, EMS, SM4DC | CCTV, SKD, SSWIN, EMS, SM4DC |
Ligthing | Out/In/Ewak | Out/In/Ewak | Out/In/Ewak | Out/In/Ewak |
Documentaction Warranty Availability | Technical Documentation 2Y 8-12 weeks | Technical Documentation 2Y 8-12 weeks | Technical Documentation 2Y 8-12 weeks | Technical Documentation 2Y 8-12 weeks |
An example of a RACKS layout that can be freely configured depending on the needs.
Sample Container DataCenter
Reference range:
- Technical container; sandwich panels; REI60, door 200x100 smoke resistant, RC3
- Separate receiving electrical installations for: IT, cooling systems, indoor/outdoor lighting, evacuation; RGCDC(Container main switchboard): IN250A, 3 ATS supply lines, energy analyzer, separate receiving sections, 2xEPO
- Fire safety systems: NOVEC- fire extinguishing system, VESDA early detection system, unloading system.
- Electronic security systems: CCTV (2MP cameras, internal / external, vandal-proof, Alarm S, ACS.
- ICT system: 4DC server RACK system equipped with PDU BPS series, EMS environmental monitoring system, one-way-row-cube(aisle), mechanical door system
- UPS Modular (N + 1) uninterruptible system with battery ste (8-10min backup time) in 4DC RACK.
- BKTiROWDX,(N + 1) row cooling system
- A visualization system integrates technical equipment systems with a wall-mounted touch panel along with LAN cabling.
- The generator set ready
DC container with a vestibule with EI30 fire resistance.
- 6 x 4DC RACK 800x1200 42U( One of them UPS), Cold Aisle (150cm) direct entry (door 140x200)
Power load: 5kW per RACK
ICT system cabling duct 4DC
Row cooling system BKTiROWDX 2x25kW (N+1).
Monitoring PDU BPS2000 4xIEC320 C13 + 6xIEC320 C19.
EMS environmental monitoring system – liquid, fire, temperature, humanity detection
System Manager 4 DC A visualization system integrates technical equipment systems, GSM alerting, a wall-mounted touch panel along with LAN cabling.
Main switchboard of the container - 250A, 2x EPO (main, UPS)
UPS backup power supply system (power backup for IT systems and air conditioning on one UPS):IT- 50kVA N+1 (2x25+25kW) modular, battery set (separately for each module) 8 minutes for a load of 23kW (8min @ 46kW).
Fire extinguishing and detection system VESDA, Inergen iFLOW®; 1 tank 140l, Ignis fire system
Generator set with a capacity of 66kVA LTP / 60kVA PRP, 1500rpm, 50Hz, 400Vac / 230Vac, in a soundproofed housing, IVECO engine with a mechanical speed controller.
Alarm system, access control and video monitoring
Steel structure containers with a sandwich panel, EI60 fire resistance, RC3 class entrance doors and ROXTEC class culverts
Container SET - example configurations: CDC container assembly divided into two independent spaces