Container DataCenter Configuration

 

 

 

 
SIZE CDC  Container 6x3x3m E30/60 steel structure, Door100x200, RC3, Roxtec, StairsContainer 6x3x3m E30/60 steel structure, Door100x200, RC3, Roxtec, StairsContainer 6x3x3m E30/60 steel structure, Door100x200, RC3, Roxtec, StairsContainer 6x3x3m E30/60 steel structure, Door100x200, RC3, Roxtec, Stairs
Moc IT10kW15kW20kW30-40kW
Power Supply / UPS

RGCDC Cab 250A,

Backup PS-ATS, 2xEPO, Generator
UPS 15kW module, N+1, 8min,

BPS2000,

RGCDC Cab 250A,

Backup PS-ATS, 2xEPO, Generator
UPS 20kW module, N+1, 8min,

BPS2000,

RGCDC Cab 250A,

Backup PS-ATS, 2xEPO, Generator
UPS 40kW module, N+1, 8min,

BPS2000,

RGCDC Cab 250A,

Backup PS-ATS, 2xEPO, Generator
UPS 50kW module, N+1, 8min,

BPS2000,

Cooling12kW, iROW N+1,
wall-mounted condensers
17kW, iROW N+1,
roof condensers
21kW, iROW N+1,
roof condensers
40kW, iROW N+1,
roof condensers
Fire protectionInergen/Novec/FM200Inergen/Novec/FM200Inergen/Novec/FM200Inergen/Novec/FM200
IT-RACK-st4CUBEDC
4x4DC42U600(3kW)
+ 1xRACK-UPS
4CUBEDC
4x4DC42U600(3,5kW)
+ 1xRACK-UPS
4CUBEDC
4x4DC42U600(5kW)
+ 1xRACK-UPS
4CUBEDC
4x4DC42U600(7,5kW)
+ 1xRACK-UPS
SecurityCCTV, SKD, SSWIN, EMS, SM4DCCCTV, SKD, SSWIN, EMS, SM4DCCCTV, SKD, SSWIN, EMS, SM4DCCCTV, SKD, SSWIN, EMS, SM4DC
LigthingOut/In/EwakOut/In/EwakOut/In/EwakOut/In/Ewak
Documentaction
Warranty
Availability

Technical Documentation

2Y

8-12 weeks

Technical Documentation

2Y

8-12 weeks

Technical Documentation

2Y

8-12 weeks

Technical Documentation

2Y

8-12 weeks

 

 

An example of a RACKS layout that can be freely configured depending on the needs.

 

 

 

Sample Container DataCenter

 

 

 

 

Reference range:

 

  • Technical container; sandwich panels; REI60, door 200x100 smoke resistant, RC3
  • Separate receiving electrical installations for: IT, cooling systems, indoor/outdoor lighting, evacuation; RGCDC(Container main switchboard): IN250A, 3 ATS supply lines, energy analyzer, separate receiving sections, 2xEPO
  • Fire safety systems: NOVEC- fire extinguishing system, VESDA early detection system, unloading system.
  • Electronic security systems: CCTV (2MP cameras, internal / external, vandal-proof, Alarm S, ACS.
  • ICT system: 4DC server RACK system equipped with PDU BPS series, EMS environmental monitoring system, one-way-row-cube(aisle), mechanical door system
  • UPS Modular (N + 1) uninterruptible system with battery ste (8-10min backup time) in 4DC RACK.
  • BKTiROWDX,(N + 1) row cooling system
  • A visualization system integrates technical equipment systems with a wall-mounted touch panel along with LAN cabling.
  • The generator set ready

 

 

 

 

DC container with a vestibule with EI30 fire resistance.

 

 

 

 

 

 

 

 

 

  • 6 x 4DC RACK 800x1200 42U( One of them UPS), Cold Aisle (150cm) direct entry (door 140x200)
  • Power load: 5kW per RACK

  • ICT system cabling duct 4DC

  • Row cooling system BKTiROWDX 2x25kW (N+1).

  • Monitoring PDU BPS2000 4xIEC320 C13 + 6xIEC320 C19.

  • EMS environmental monitoring system – liquid, fire, temperature, humanity detection

  • System Manager 4 DC A visualization system integrates technical equipment systems, GSM alerting,  a wall-mounted touch panel along with LAN cabling.

  • Main switchboard of the container - 250A, 2x EPO (main, UPS)

  • UPS backup power supply system (power backup for IT systems and air conditioning on one UPS):IT- 50kVA N+1 (2x25+25kW) modular,  battery set (separately for each module) 8 minutes for a load of 23kW (8min @ 46kW).

  • Fire extinguishing and detection system VESDA, Inergen iFLOW®; 1 tank 140l, Ignis fire system

  • Generator set with a capacity of 66kVA LTP / 60kVA PRP, 1500rpm, 50Hz, 400Vac / 230Vac, in a soundproofed housing, IVECO engine with a mechanical speed controller.

  • Alarm system, access control and video monitoring


Steel structure containers with a sandwich panel,  EI60 fire resistance, RC3 class entrance doors and ROXTEC class culverts

 

 

Container SET - example configurations: CDC container assembly divided into two independent spaces
 

 

 

 

 

 

 

 

zamknij
Ladies and Gentlemen, in order to provide services at the highest level, as part of our service we use cookies. Using the site without changing the settings for cookies is that they will be posted in your terminal. If you do not agree, please feel free to make appropriate changes in the settings of your web browser.